6 • Model 1017-03 Operator’s ManualCAUTION: Do not route controller power and detector wiring through the same conduit hub. The power cable may disru
Model 1017-03 Operator’s Manual • 7Start UpThis section describes procedures to start up the Model 1017-03 and place it into normal operation.Introd
8 • Model 1017-03 Operator’s ManualMaintenanceThis section describes maintenance procedures. It includes preventive maintenance procedures. This sect
Model 1017-03 Operator’s Manual • 9Probable causes• The calibration cylinder is low, out-dated, or defective.• The Model 1017-03’s flow rate is too
10 • Model 1017-03 Operator’s ManualNOTE: Make sure the bottom ferrule is laying flat in the nut.4. Insert the cone-shaped front ferrule on top of th
Model 1017-03 Operator’s Manual • 113. Allow the Model 1017-03 to draw sample for one minute.4. Follow the directions in the controller’s operator’s
Model 1017-03 Operator’s ManualWARNINGRead and understand this instruction manual before operating instrument. Improper use of the gas monitor could
Model 1017-03 Operator’s ManualWarrantyRKI Instruments, Inc. warranties gas alarm equipment manufactured by RKI and sold by RKI to be free from defec
Model 1017-03 Operator’s ManualTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model 1017-03 Operator’s Manual • 1Sample-Draw Combustible Gas DetectionOverviewThis manual describes the Model 1017-03 sample draw combustible gas
2 • Model 1017-03 Operator’s ManualDescriptionThis section describes the components of the Model 1017-03. The Model 1017-03 consists of the housing a
Model 1017-03 Operator’s Manual • 3Figure 2: Model 1017-03 Flow DiagramSubpanel AssemblyAll the internal components of the Model 1017-03 are part o
4 • Model 1017-03 Operator’s ManualInstallationThis section describes procedures to mount the Model 1017-03 in the monitoring environment and wire it
Model 1017-03 Operator’s Manual • 5Connecting the Sample Lines to the Model 1017-031. Attach 1/4 inch O.D. rigid sample tubing to the INLET fitting.