Eclipse Detector Head Operator’s Manual Eclipse Detector HeadOperator’s Manual Part Number: 71-0036RKRevision; 0Released: 3/12/03
10 Eclipse Detector Head Operator’s Manual6. Guide a three-conductor, shielded cable or three wires in conduit through the top conduit hub of the j
Eclipse Detector Head Operator’s Manual 11Verify that the transmitter is in a fresh air environment (environment known to be free of the target gas a
Eclipse Detector Head Operator’s Manual 12NOTE: If there is no switch activity for 5 minutes while the screen indicates that the unit is ready for a
Eclipse Detector Head Operator’s Manual 13green wire to terminal labelled LEL GRN, black wire to terminal labelled LEL BLK.• CO or H2S gas detector.R
Eclipse Detector Head Operator’s Manual 14Calibration, Combustible and Toxic VersionsThis section describes how to calibrate the combustible gas and
Eclipse Detector Head Operator’s Manual 15Setting the Zero Reading1. Verify that the gas reading has stabilized.2. Press and release the optical swit
Eclipse Detector Head Operator’s Manual 16Calibration, Oxygen VersionThis section describes how to calibrate the oxygen version of the Eclipse. It in
Eclipse Detector Head Operator’s Manual 17Setting the Response ReadingNOTE: The following procedure assumes that the oxygen content is not normal (20
Eclipse Detector Head Operator’s Manual 18Parts ListTable 6 lists replacement parts and accessories for the Eclipse Detector Head.Table 2: Parts List
2 Eclipse Detector Head Operator’s Manual Warranty RKI Instruments, Inc., warranties gas alarm equipment manufactured by RKI and sold by RKI to b
Eclipse Detector Head Operator’s Manual 3 About the Eclipse Detector Head The Eclipse Detector Head is a fixed mounted, continuous-monitoring detect
4 Eclipse Detector Head Operator’s Manual Description Figure 1: Eclipse Component Location The Eclipse consists of the gas detector, amplifier set
Eclipse Detector Head Operator’s Manual 5 detector terminal strip and power/signal terminal strip. A ribbon cable with a connector on each end conn
6 Eclipse Detector Head Operator’s Manual in the upper right of the display.If the Eclipse is installed in an area with no significant background
Eclipse Detector Head Operator’s Manual 7 Figure 2: Outline & Mounting Dimensions, LELFigure 3: Outline & Mounting Dimensions, HS/CO4.603/4
8 Eclipse Detector Head Operator’s Manual Figure 4: Outline & Mounting Dimensions, Oxygen Wiring the Eclipse WARNING: Always verify that the
Eclipse Detector Head Operator’s Manual 9 Figure 6: LEL Detector Wiring • CO or H 2 S gas detector.Red wire to terminal labeled TOXIC RED, black wi